Measurement-based electrical parameters of power transformers for Frequency Response Analysis interpretation - Part I: Core analysis

For purpose of FRA interpretation in practical manner, electrical parameters of power transformers in a physical equivalent circuit should be determined. As a first step, the paper introduces a new approach in determining frequency dependent core impedances of a distribution transformer based on the combination of circuit analysis of a duality-based model, measurements of driving-point impedances and experimental formulas. | Tạp chí Phát triển Khoa học và Công nghệ, tập 20, số K3-2017 5 Measurement-based electrical parameters of power transformers for Frequency Response Analysis interpretation Part I: Core analysis Dinh Anh Khoi Pham Abstract—Although the standard Frequency Response Analysis (FRA) test has been approved as an efficient tool to diagnose mechanical failures in power transformers, the demand to interpret FRA traces in practical and physical way is still requested. That means physical electrical parameters of transformers should be determined reasonably based on real measurements and afterwards are applicable for the interpretation. For purpose of FRA interpretation in practical manner, electrical parameters of power transformers in a physical equivalent circuit should be determined. As a first step, the paper introduces a new approach in determining frequency dependent core impedances of a distribution transformer based on the combination of circuit analysis of a duality-based model, measurements of driving-point impedances and experimental formulas. From that, two important contributions can be drawn. Firstly, frequency dependent core impedances are ready as available components in the circuit for FRA interpretation in broad frequency range. Secondly, the core parameters could be useful indicators for detecting relevant failures in cases there is no more failure on transformer windings. Index Terms—Driving-point impedance, duality principle, electrical parameters, frequency response analysis, transformer core. 1 INTRODUCTION T he core is an important component of power transformers, which provides magnetic links between the windings. Its magnetic property has been so far investigated in detail through Manuscript Received on March 15th, 2017, Manuscript Revised on November 01st, 2017. Dinh Anh Khoi Pham, Division of High-Voltage Engineering, Department of Power Systems, Faculty of Electrical and Electronic Engineering, Ho Chi Minh City University of .

Không thể tạo bản xem trước, hãy bấm tải xuống
TÀI LIỆU LIÊN QUAN
TỪ KHÓA LIÊN QUAN
TÀI LIỆU MỚI ĐĂNG
192    105    8    29-04-2024
Đã phát hiện trình chặn quảng cáo AdBlock
Trang web này phụ thuộc vào doanh thu từ số lần hiển thị quảng cáo để tồn tại. Vui lòng tắt trình chặn quảng cáo của bạn hoặc tạm dừng tính năng chặn quảng cáo cho trang web này.