Chương 5. CPU 5,1 Thông số kỹ thuật Bảng sau đây cho thấy các thông số kỹ thuật chung của dòng Master-K80S Thông số kỹ thuật K7M-DR10S khoản K7M-DR10S/DC K7M-DR20S/DC K7M-DR30S/DC K7M-DR40S/DC K7M-DR60S/DC K7M-DT10S phương pháp Chương trình kiểm soát I / O phương pháp kiểm soát Chương trình ngôn ngữ số các hướng dẫn xử lý tốc độ chương trình công suất I / O điểm PMKL bộ nhớ thiết bị T 10msec: | Chapters CPU Module Chapter 5. CPU Specifications The following table shows the general specifications of the MASTER-K80S series Item Specifications Remarks K7M-DR10S K7M-DR20S K7M-DR30S K7M-DR40S K7M-DR60S K7M-DR10S DC K7M-DR20S DC K7M-DR30S DC K7M-DR40S DC K7M-DR60S DC K7M-DT10S K7M-DT20S K7M-DT30S K7M-DT40S K7M-DT60S Program control method Cycle execution of stored program Time-driven interrupt Process-driven interrupt I O control method Indirect mode Refresh method Direct by program command Program language Mnemonic Ladder diagram Numbers of instructions Basic 30 Application 218 Processing speed Ư Program capacity I O points 10 2 40 60 Memory device P I O relay M M000 M191F 3 072p oints Auxiliary relay K K000 K31F 512 points Keep relay L L000 L63F 1 024 points Link relay F F000 F63F 1 024 points Special relay T 100msec T000 T191 192 points 10msec T192 T255 64 points Timer C C000 C255 256 points Counter S 100x100 steps Step controller D D0000 D4999 5 000 words Data register Operation modes RUN STOP PAUSE DEBUG Self-diagnosis functions Detect errors of scan time memory I O battery and power supply Data back-up method Battery-back-up Max. expansion level Up to 3 level 5-1 Chapters CPU Module Item Specifications Remarks Internal Function PID control function Function block control auto tuning forced output adjustable operation scan time forward reverse operation control Cnet I F Function Master-K exclusive protocol support MODBUS protocol support User s protocol support J Common use with KGLWIN port Highspeed counter Capacity 1 phase 16 kHz 1 channel 2 phase 8 kHz 1 channel Counter function It has 3diffferant counter function as following 1 phase up down by program 1 phase up down by B phase input 2 phase up down by phase difference Multiplication function Multiplication 1 2 or 4 adjustable Data comparison function Execute a task program when the elapsed counter value reaches to the preset value Pulse catch Minimum pulse width 8 points .